| Model |
HZ1241100AO(On Grid) |
| DC Battery Parameters |
DC Battery Parameters |
| Battery Rated Energy(KWh) |
241 |
| Battery Rated Voltage (V) |
768 |
| Battery Voltage Range(V) |
696-852 |
| Battery Type |
LFP |
| Battery Energy(Ah) |
314 |
| Battery Life Cycle |
6,000 Cycles(0.5C,5%~95%DOD,80%SOH) |
| Battery Standard Charge/Discharge Rate(C) |
0.5 |
| Battery Pack Series And Parallel |
1P24OS |
| Module Cooling Method |
Air Cooling |
| AC Parameters |
AC Parameters |
| Rated AC Power(KW) |
100 |
| Maximum Power(KW) |
110 |
| Maximum Current(A) |
160 |
| Rated AC Voltage(V) |
400 |
| AC Voltage Range |
±15% |
| Rated AC Frequency(Hz) |
50/60 |
| Wiring Method |
3P+N+PE |
| Current Distortion Rate THDI |
<3%(Rated Power) |
| Power Factor |
≥0.99/-1-1 |
| Voltage Total Harmonic Distortion THDU |
<3%(Linear Load) |
| PCS Cooling Method |
Air Cooling |
| Maximum Efficiency |
98.5% |
| System Parameters |
System Parameters |
| Energy Cycle Efficiency |
≥90% |
| Protection Level |
IP54 |
| Corrosion Resistance Level |
C3 is the default,C4/C5 are optional |
| Fire Fighting |
Aerosol/Perfluorohexanone(Optional) |
| Isolation Method |
Not Isolated(Transformer Optional) |
| Relative Humidity |
0~95%(Non-condensing) |
| Ambient Temperature |
-30℃~55℃(Derating Above 45℃) |
| Altitude |
<3000m(Derating Applies Over 2000m) |
| BMS Communication |
CAN |
| EMS Communications |
4G/CAN/RS485 |
| Dimensions(W×D×H)MM |
1050*1330*2400 |
| Weight(T) |
2.6 |
| Annual Decay Rate |
<3% |
| Warranty |
5 years |