I. Features
1. VRLA gel battery with advanced technology
2. No free electrolyte, no acid mist, maintenance-free
3. Suitable for solar, wind, telecom, UPS, etc.
4. Float design life over 8 years
5. Low self-discharge (≤3%/month), suitable for long storage
II. Technical Parameters
| Rated Voltage |
12V |
| Rated Capacity (10hr, 1.80V/cell, 25°C) |
120Ah |
| Weight |
32Kg |
| Max Discharge Current |
30I10A (3min) |
| Max Charge Current |
≤0.25C10 |
| Self-discharge (25°C) |
≤3%/month |
| Case Material |
ABS |
| Dimensions (L×W×H) |
405×173×231mm |
| Total Height with Terminals |
231mm |
III. Operating Conditions
| Temperature Range |
Discharge: -45°C~50°C Charge: -20°C~45°C Storage: -30°C~40°C |
| Charge Voltage (25°C) |
Float: 13.5V-13.8V Equalize: 14.4V-14.8V |
| Charge Method (25°C) |
Float: 2.275±0.025V/Cell, ±3mV/Cell °C Cycle: 2.45±0.05V/Cell, ±5mV/Cell °C |
| Temp vs Capacity |
105% @ 40°C 82% @ 0°C 68% @ -20°C |
IV. Discharge Current (A, 25°C) at Different Cut-off Voltages & Discharge Durations
| Cut-off Voltage (V/Cell) |
1H |
3H |
5H |
10H |
20H |
50H |
100H |
120H |
240H |
| 1.70 |
63.72 |
28.96 |
19.35 |
12.49 |
6.45 |
2.71 |
1.47 |
1.31 |
0.68 |
| 1.75 |
62.45 |
28.67 |
19.02 |
12.31 |
6.30 |
2.60 |
1.38 |
1.21 |
0.63 |
| 1.80 |
61.20 |
28.40 |
18.72 |
12.00 |
6.15 |
2.52 |
1.32 |
1.14 |
0.61 |
| 1.85 |
58.75 |
28.23 |
18.36 |
11.51 |
5.85 |
2.41 |
1.23 |
1.06 |
0.55 |
| 1.90 |
56.41 |
27.99 |
18.08 |
11.26 |
5.75 |
2.34 |
1.19 |
1.02 |
0.52 |
| 1.95 |
53.93 |
27.43 |
17.71 |
11.84 |
5.35 |
2.17 |
1.13 |
0.97 |
0.49 |
V. Certifications
• IEC 61427-2005
• GB/T 19001-2016 idt ISO 9001:2015
• EN IEC 61000-6-2:2019, EN IEC 61000-6-4:2019
• EN IEC 61000-3-2:2019+A1:2021
• IEC 61000-3-2:2013+AI:2019
Product dimensions and specifications are subject to change without notice. Please refer to the latest physical product for final details.